Fire‑fighting smoke exhaust fans require periodic maintenance and protection after a period of operation.
- Cut off the main power supply and place warning signs. Verify that the motor grounding of fire ventilation equipment is properly connected.
- Check whether the insulation resistance of the fan motor meets specifications. Inspect main‑circuit connectors. Replace connectors if contacts are severely worn (worn down to one‑third of original thickness).
- Inspect and replace gaskets and sealing fillers between mating surfaces.
- Adjust the tension of the drive belt. Rotate the impeller manually to check for abnormal wobble. Examine and tighten all screws and couplings.
- Apply proper lubricating oil to moving parts to guarantee flexibility and stability of couplings and bearings.
- Verify that the damper of fire ventilation equipment operates reliably and flexibly, with clear opening‑angle indicators.
- Clean the motor, impeller, filter and inner housing.
- Check that components inside the remote‑control cabinet are in good condition.
- Manually power on the unit. Confirm indicator lamps, voltage and ammeter readings are normal. Listen for unusual noise and check whether three‑phase current is balanced.
- Perform three consecutive start‑stop cycles to test reliable remote‑control function of the fire‑fighting smoke exhaust fan.
- Run a two‑hour trial operation. Monitor bearing temperature and motor temperature rise to ensure normal fan performance.